Function
Amseco
Sync Mode*
®
Gentex
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
®
System Sensor
Sync Mode*
System Sensor is a
registered trademark
of Honeywell.
®
CooperWheelock
Sync Mode*
CooperWheelock is a
registered trademark
of Cooper Wheelock.
*Note: The AL1002ADA220 will only synchronize horns, horn/strobes and strobes that contain synchronization
capability. Contact signal manufacturer for more detailed info.
The same synchronization mode must be selected for all outputs
Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1) and audible
notification appliances (horns) via Input 2 (IN2). This allows audible notification appliances (horns)
to be silenced while visual notification appliances (strobes) continue to operate.
Amount of Notification Appliances per NAC:
Amseco
®
Gentex
*Not to exceed a maximum of 2.5A per NAC.
AL1002ADA220 Installation Guide
Sync Mode Selection Table:
Switch Positions
Descriptions
ON
OFF
This mode is designed to work with the Amseco series of horns,
strobes, and horn/strobes to provide a means of synchronizing the
1, 3,
2
Temporal-coded horns, synchronizing the flash timing of the strobe,
4
and allowing audible notification appliances (horns) and visual notifica-
tion appliances (strobes) to be silenced/ deactivated at the same time.
This mode is designed to work with the Gentex
strobes, and horn/strobes to provide a means of synchronizing the
1, 2,
Temporal-coded horns, synchronizing the flash timing of the strobe,
3, 4
and allowing audible notification appliances (horns) and visual notifica-
tion appliances (strobes) to be silenced/ deactivated at the same time.
This mode is designed to work with the System Sensor
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing
1, 2, 4
3
of the strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silenced/ deactivated at
the same time.
This mode is designed to work with the CooperWheelock series of
horns, strobes, and horn/strobes to provide a means of synchronizing
the Temporal-coded horns, synchronizing the one-second flash timing
2, 3, 4
1
of the strobe, and allowing audible notification appliances (horns) and
visual notification appliances (strobes) to be silenced/ deactivated at
the same time.
27 per NAC*
32 per NAC*
®
System Sensor
®
CooperWheelock
®
32 per NAC*
32 per NAC*
series of horns,
®
series of
- 5 -