Galvin Engineering CliniLever TC51FC1C Installations-Manuale - Seite 3

Blättern Sie online oder laden Sie pdf Installations-Manuale für Hilfe für das Badezimmer Galvin Engineering CliniLever TC51FC1C herunter. Galvin Engineering CliniLever TC51FC1C 4 Seiten. Cp-bs hospital wall mixing set type 51 fixed 150 c/d

Product Installation Guidelines
®
3. CliniLever
body
Check maintenance tails to ensure o-rings are
fitted correctly and are in good condition.
Fit the CliniLever
tails until it sits flush against them, taking care
not to damage the o-rings.
TROUBLESHOOTING
PROBLEM
Taps are dripping water
Water is not flowing from tap
Handle is loose
Flange does not screw down
onto basin/sink surface
© Galvin Engineering Pty Ltd
®
body onto the maintenance
CAUSE
Ceramic discs are worn or damaged
Tap seat is damaged
Water is turned off
Aerator or flow regulator is blocked
by debris
Screw has come loose
Tap bodies are set too far out
4. Fit grub screws and testing
Ensure the CliniLever
against the maintenance tail and then secure
in place with the supplied grub screws.
ENSURE ALL FOUR (4) GRUB SCREWS
ARE FITTED WITH SUPPLIED ALLEN KEY.
If grub screws are missing, contact us on
1300 514 074.
Once grub screws are secure, open the
regulating valve prior to the tap. Open the
lever handles and ensure there is flow from
both hot and cold inlets. Inspect the tap and
check for any leaks.
RECTIFICATION
Remove and inspect SBA.
Remove debris and/or replace
SBA if damaged.
Refurbish tap seat using a
reseating tool.
Turn water on
Remove aerator and/or flow
regulator from tap and remove
debris. Install an inline strainer.
Tighten handle screw
Re-position tap bodies and breach
piece
Version 3, 27 August 2021, Page 3 of 4
®
body is pushed firmly