ELECTRICAL CONNECTIONS
STEP 1:
NOTE: USE MIN. 90°C SUPPLY CONDUCTORS for 120-277V
luminaires and USE MIN 75°C SUPPLY CONDUCTORS for the
347V luminaires.
Make the following Electrical Connections for products rated
120V, 277V, or 347V (Line-Neutral), or rated 208V, or 240V
(Line-Line):
a. For products rated 120V, 277V or 347V, connect the Black
lead from the luminaire to the LINE supply wiring inside
the junction box or for products rated 208V, or 240V,
connect to the HOT 1 supply wiring.
b. For products rated 120V, 277V or 347V, connect the White
lead from the luminaire to the NEUTRAL supply wiring
inside the junction box or for products rated 208V, or
240V, connect to the HOT 2 supply wiring.
c. Connect the Green or Green/Yellow lead from the
luminaire to the GROUND supply wiring inside the
junction box.
STEP 2:
The Blue/White low-voltage wires are used to override the
luminaire to full output. They may be connected to third-party
equipment to provide an override signal to the luminaire. Do not
wire the Blue/White wires to high-voltage. The wires should be
capped if not being used.
• SHORT: Luminaire overrides to full output
• OPEN: Luminaire operates normally
© 2019 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree
registered trademarks of Cree, Inc.
4 of 4
LINE
OR HOT 1
GREEN
NEUTRAL
OR HOT 2
®
and the Cree logo are
LUMINAIRE
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
BLUE W/WHITE
BLUE W/WHITE
www.creelighting.com