Address
Description
Data type #
40547
TSET
REAL
40549
SETTING
UINT16
40550
MATRIX
UINT8
40551
LIMITA
UINT8
14
Default
Description
1.0
Settling time (99%) [s] (1 ... 30)
Automatic parameter correction
00h
Settings
Bit
Description
0
Recognition of the type of connection (2L, 3L, 4L) after reset
1
Input 1: Breakage monitoring activated
2
Input 2: Breakage monitoring activated
3
Input 1: Short circuit monitoring activated
4
Input 2: Short circuit monitoring activated
Linking of inputs with outputs
0
01h
Output 1:
00h:
Not used
01h:
Input 1
02h:
Input 2
03h:
Input 1 + 2
04h:
Input 1 – 2
05h:
Input 2 – 1
06h:
Input 1 * 2
07h:
Minimum value (Input 1,2)
08h:
Maximum value (Input 1,2)
09h:
Mean value (Input 1,2)
81h:
Sensor redundancy: Input 1 normally
82h:
Sensor redundancy: Input 2 normally
87h:
Sensor redundancy: Minimum value (Input 1,2)
88h:
Sensor redundancy: Maximum value (Input 1,2)
89h:
Sensor redundancy: Mean value (Input 1,2)
- Only measured variables of the same unit may be linked.
- Product formation: Only possible for combinations V*mV, V*mA, mA*mA, mV*mA and mV*mV.
Sensor redundancy
- Measured variable in case of a fault:
INPUTx which does not show a fault
- Limitations:
- The same measuring range for both inputs
- The same scaling factors (always 1.0)
- No output value in case of a fault
- Temperature measurement
- Breakage or short circuit monitoring active
1
00h
Output 2 (same as Output 1)
at 2xmA:
02h
Setting of limit values
0
0
Measured variable for Limit value 1
Bit
Description
0-4
Limit value
6
Absolute value of measured variable for the limit value
7
1: Gradient dx/dt
Note: Drift monitoring is realised by difference calculation.
Only measured variables of the same unit may be linked.
1
0
Measure variable for Limit value 2 (same as Limit value 1)
Operating instructions V604s Be
2
0: Not used
1: Input 1 (INPUT1)
2: Input 2 (INPUT2)
3: Measured variable Output 1 (MEAS1)
4: Measured variable Output 2 (MEAS2)
5: Input 1 – Input 2
6: Input 2 – Input 1
Camille Bauer