Description
Data type #
40552
ALARMSETA
UINT8
40553
TON
REAL
40555
TOFF
REAL
40557
TONLIMITA
REAL
40559
TOFFLIMITA
REAL
40561
LIMIT10N
REAL
40563
LIMIT10FF
REAL
40565
LIMIT2ON
REAL
40567
LIMIT2OFF
REAL
40569
OUTSET1
UINT16
40570
OUTRANGE1
REAL
40574
TRIM1
REAL
40578
ERRVAL1
REAL
Camille Bauer
Default
Description
Relay and alarm (Relay 1)
0
00h
Relay 1, LED relay 1
Bit
Description
0
Limit value 1
1
Limit value 2
2
Sensor breakage Input 1 or 2
3
Sensor short circuit Input 1 or 2
7
Inverted
These settings may all be combined with each other.
1
00h
Alarm 1, LED alarm
Bit
Description
0
Limit value 1
1
Limit value 2
2
Sensor breakage Input 1 or 2
3
Sensor short circuit Input 1 or 2
These settings may all be combined with each other.
0.0
Alarms rise delay [s]: 0..60
0.0
Alarms drop delay [s]: 0..60
0.0
Limit values 1,2: rise delay [s]: 0..3600
0.0
Limit values 1,2: drop delay [s]: 0..3600
0.0
Switching-on threshold Limit value 1, unit of LIMIT1
0.0
Switching-off threshold Limit value 1, unit of LIMIT1
0.0
Switching-on threshold Limit value 2, unit of LIMIT2
0.0
Switching-off threshold Limit value 2, unit of LIMIT2
05h
Output settings Output 1
at VB604s
Bit
Description
01h
0-1
Output limit
0: ±0 mA or 0 V
1: ±1 mA or 0.5 V
2: ±2 mA or 1 V
3: –0.2/+0.5 mA or –0.1/+0.25 V (e.g. 3.8 mA ... 20.5 mA)
2
Signal fl ow
0: Interrupted (only possible with VB604s)
1: Activated (V604s)
3
Output confi guration
0: Current output
1: Voltage output
4
Inverting
5
Table
6-7
Output in case of a fault
0: PERCENTx,
1: ERRVALx in case of fault Input 1
2: ERRVALx in case of fault Input 2
3: ERRVALx in case of fault Input 1 or 2
8-15
Transmission function
0: User-defi ned
1: Linear
2: Quadratic
3: Volume of a horizontal cylinder
Output range Output 1
2
Automatic parameter correction
0
4.0
Minimum value
1
20.0
Maximum value
Output trimming Output 1
2
Automatic parameter correction
0
0.0
Offset trimming
[in % of the output range, setting range +/– 10%]
1
100.0
Gain trimming
[in % of the output range, setting range 90...110%]
0.0
Output value Output 1 in case of a fault
[in % of the output range, setting range -10...+110%)
Operating instructions V604s Be
0: normal, 1: inverted
0: without, 1: with table
–20...20 [mA] / –10...10 [V]
–20...20 [mA] / –10...10 [V]
1
1
1
15