eGauge EG4 Series Schnellstart-Handbuch - Seite 12
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Messgeräte eGauge EG4 Series herunter. eGauge EG4 Series 12 Seiten.
Phasing Information
To measure power, the eGauge meter uses
amperage measurements collected by current
transformers (CTs) and voltage phases connected
to the line inputs. Every phase from the service
must be connected to the eGauge, as well as a
neutral. Single/split phase service requires L1 and
L2, while 3-phase service requires L1, L2, and L3.
The phase connected to the L1 line input of
the eGauge meter should be the same as the
system L1, or a "phase mix-up" may occur when
calculating power using the CT measurements
and power measurements will be incorrect.
For more information about phasing and example
diagrams, please visit
eGauge.net/support/phasing.
12