Baumer AMG11 N29 Manual - Página 11
Navegue en línea o descargue pdf Manual para Media Converter Baumer AMG11 N29. Baumer AMG11 N29 41 páginas. Absolute encoders with profinet interface
4.3.3.
Manual name assignment
To perform an I/O system network scan, go to „PLC" – „Edit Ethernet Node" – „Browse". The scan provides
all bus nodes. In the example the PLC and encoder „encoder01" was found.
The MAC address serves as a unique identifier. When clicking the button „Flash" the highlighted device will
flash its status-LED so it can be found easily amongst other devices.
A double-click on the desired line (here: encoder "encoder01") opens the window "Edit Ethernet Node"
Enter the new name required for configuration in line „Device name". Click "Assign name" to execute. After
this, the encoder will immediately be recognized with this name in the PROFINET Network.
Baumer_BUDE-PROFINET_MA_EN.docx
14.06.2016 / bja
11/41
www.baumer.com