Baumer AMG11 N29 Manuel - Page 11

Parcourez en ligne ou téléchargez le pdf Manuel pour {nom_de_la_catégorie} Baumer AMG11 N29. Baumer AMG11 N29 41 pages. Absolute encoders with profinet interface

Baumer AMG11 N29 Manuel
4.3.3.

Manual name assignment

To perform an I/O system network scan, go to „PLC" – „Edit Ethernet Node" – „Browse". The scan provides
all bus nodes. In the example the PLC and encoder „encoder01" was found.
The MAC address serves as a unique identifier. When clicking the button „Flash" the highlighted device will
flash its status-LED so it can be found easily amongst other devices.
A double-click on the desired line (here: encoder "encoder01") opens the window "Edit Ethernet Node"
Enter the new name required for configuration in line „Device name". Click "Assign name" to execute. After
this, the encoder will immediately be recognized with this name in the PROFINET Network.
Baumer_BUDE-PROFINET_MA_EN.docx
14.06.2016 / bja
11/41
www.baumer.com