Automated Logic S6104 Instrucciones técnicas - Página 16

Navegue en línea o descargue pdf Instrucciones técnicas para Unidad de control Automated Logic S6104. Automated Logic S6104 16 páginas.

Run
S6104
Control Module
A
U TO M A TE D
C O R P O R A T I O N
CMnet
Tx
CMnet
Rx
Figure 17. S6104 LED locations
Power - indicates power is being supplied to
the module.
CMnet Tx - lights when the module transmits
data over the CMnet.
CMnet Rx - lights when the module receives
data from the CMnet.
Digital Output Status - lights when the digital
output is activated.
Analog Output Status - lights when the
analog output is activated.
Table 9. LED Signals
Run LED
Error LED
2 flashes
Off
per second
2 flashes
1 flash,
per second
then pause
2 flashes
2 flashes
per second
alternating
with LED
2 flashes
2 flashes in
per second
sync with
LED, then
pause
2 flashes
3 flashes,
per second
then off
Revised 7/30/02 • S6104
Error
Power
Digital Output
Status
1 2
1 1
L
OGI C
Analog Output
Status
Condition
Normal
Normal, but module is
alone on the CMnet
(this sequence doesn't
occur in WebCTRL)
Five minute auto-restart
delay after system error
Module is configured for a
different baud rate than the
rest of the network
segment
Module has just been
formatted
Table 9. LED Signals (Continued)
Run LED
Error LED
2 flashes
4 flashes,
per second
then pause
2 flashes
On
per second
5 flashes
On
per second
5 flashes
Off
per second
7 flashes
7 flashes
per second
per second,
alternating
with LED
14 flashes
14 flashes
per second
per second,
alternating
with LED
Protection
The S6104 module is protected by internal
solid state Polyswitches on the incoming
power and network connections. These
Polyswitches are not replaceable and will
reset themselves if the condition that caused
the fault returns to normal.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in WebCTRL or
SuperVision. Refer to the appropriate user's
guide for more information about the module
status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
(the month digit is in hexadecimal).
16
© 2002 Automated Logic Corporation
Condition
Two or more devices on
this network have the
same ARC156 network
address
Exec halted after frequent
system errors or GFBs
halted
Exec start-up aborted, Boot
is running
Firmware transfer in
progress, Boot is running
Ten second recovery
period after brownout
Brownout