For electrodes with a length over 300 mm for the detection in non-conductive containers (sensors 
in vertical position) must be used the auxiliary electrode (e.g. conductivity probe). The auxiliary
electrode is connected to the sensor housing. Recommended length of the auxiliary electrode 
and the distance from the sensor are shown in the picture.
Suitable types of auxiliary electrode probes are e.g. Dinel CNP–18F–30 with M18 thread. 
Fig. 6: Auxiliary electrode in non-conductive tanks
7 .  e
lectrical
For  "A"  variant  with  the  fixed  cable,  the  individual  colour  cores  of  the  connecting  cable  are  con-
nected to the respective terminals of the related equipment (supply unit). 
For "C" variant with the connector, the cable can be supplied with the sensor (length 2 or 5 m), fitted 
with the pressed connector socket or dismountable connector socket without the cable (see acces-
sories). In this case the cable is connected to the inside pins of the socket according to Fig. 10.
The sensor with related equipment is interconnected by a suitable three-core (P variation) or two-
core  (S  and  R  variations)  cable.  The  length  of  the  cable  for  the  Xi  and  XiT  variations  must  be 
selected with respect to the maximum permitted parameters (usually inductance and capacity) of 
the outside intrinsically safe circuit of supply units (NSSU, NDSU, NLCU). If using a dismountable 
connector socket, the outside diameter of the cable is a maximum of 6 mm
Sensors CLS–23 are equipped with protection against over-voltages and current overload. The capacity
loads and low resistance (bulb) are evaluated by sensors with output type „P" and „S" as short circuit.
Sensors with output type „R" are designed for interconnect to intrinsically safe supply units.
In case of strong ambient electromagnetic interference, paralleling of conductors with power distribu-
tion, or for the distribution to distance over 30 m, we recommend to use shielded cable.
© Dinel, s.r.o.
CLS–23
Auxiliary electrode PDE–18
connection
Electrical connection to
the sensor housing
Applies to: CLS–23_–20, 21, 30 (for electrode length up to 300 mm)
k
k
d
d
c
Conductive probe
c
CNP–18F–30
b
b
Non-conductive tank
Ep
a
Ep
a
a
E – Electrode length in mm
E
=
20
+
20
E
=
20
+
20
E
=
40
+
40
E
=
40
+
40
E
=
10
+
50
E
=
+
10
50
E
=
40
+
20
E
=
40
+
20
>
E
>
E
E
30
+
30
E
30
+
 
30
 
9