NORMALLY CLOSED need only a probe connection. For detailed
information about timing or probe signals, refer to the section on
probe THEORY OF OPERATION.
The diagram shows a Die Sentry wired with all probes connected.
The Die Sentry has a built-in +12 Volt DC power supply to operate
the probes. The power supply is capable of supplying up to 1 AMP
of current to allow remote sensors such as proximity sensors to be
used. Make sure that the total current draw from all five probe
inputs does not exceed 1 AMP. To use the probe inputs, make sure
that the terminal labeled RET is connected to the machine's frame.
Whenever a probe input is touched to the machine, the probe circuit
will be completed and the probe input will go ON. NOTE: The probe
inputs should never be wired in a way that will connect them to
anything other than ground - Severe damage will result. Always use
DC input modules in the probe input sockets.
Limit switch inputs are not fixed and may be either AC or DC. An
AC setup is shown above. The IN CYCLE connection is optional -
Refer to the section on PROBE THEORY OF OPERATION for
information about the IN CYCLE connection