Sentry. The unused output should not be connected to anything.
USING THE DIE SENTRY
The following sections provide all of the information about the
actual operation of the Rexcon Die Sentry. The Theory of Operation
behind die protection is discussed, in addition to the OPERATION
of the Die Sentry.
DIE PROTECTION
A Die Sentry uses five probes to implement Die protection. The
probe can be used independently in one of four modes - TIMED
MODE, CAM MODE, NORMALLY OPEN, and NORMALLY
CLOSED. Unused probes can be TURNED off. In addition, there is
an optionally available program which checks to make sure that
limit switches change states on every press cycle.
The Normally Open and the Normally Closed modes are
straightforward in their operation. If a NORMALLY OPEN probe is
closed, it will cause a fault. Normally Open probes are use in
Buckle Detection. Likewise, if a Normally Closed mode is intended
as an OUT of STOCK Detection but can be used anywhere a
Normally Closed probe is needed.
TIMED and CAM modes are more complex in their operation and
are the main subject of this section. Both TIMED and CAM modes
have a set "Window" in which the probe must be seen as "ON." The
simpler of the two Modes of OPERATION is the CAM (or Limit
Switch) Mode. In this mode, when a probe's limit switch goes "ON",
an examine period begins. The examine period ends when the limit
switch goes back "OFF." The probe must be seen as "ON" before
the examine period ends. If the probe goes ON during the examine
period, the Die Sentry reports the time from the start of the examine
period until the probe goes "ON" as the probe time. If the probe is
already "ON" when the examine period begins, a probe time of
0.000 will be reported. Probe faults are generated while the device
is in SETUP MODE but the FAULT OUTPUT is always LEFT ON
(doesn't stop the press).
Here is a typical probe Timing Diagram using the CAM Mode.