7.
F
Remove Independent Temperature Shut Off board (ITSO) if installed (Figure 5).
8.
F
Remove new control panel assembly and retrofit cover panel from packaging, leaving wires
bundled together. Remove any existing sponge tape from rear of control panel door and fit new
cover panel to existing cut out (Figure 6). Ensure threaded studs on control panel door match holes
in new filler plate. Do not yet mount.
9.
Using pre-drilled holes (Figure 7), place new control panel assembly on threaded studs after cover
F
panel and mount using hardware removed from old controller panel in step four. Do not over
tighten.
Bezel assembly
mounting holes
(Red)
CONVIRON
Figure 5
Figure 6
Figure 7
CMP 6050 RETROFIT INSTALLATION INSTRUCTIONS
Control panel
assembly upper
mounting holes
(Green)
May 2013 |
257775R00
3