Dell PowerEdge 2650 Manuel d'instructions - Page 5

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions pour {nom_de_la_catégorie} Dell PowerEdge 2650. Dell PowerEdge 2650 8 pages. Activating the integrated raid controller
Également pour Dell PowerEdge 2650 : Manuel d'installation (26 pages), Manuel d'installation (32 pages), Information Update (14 pages), Manuel d'installation (20 pages), Manuel d'installation (40 pages), Manuel de remplacement (28 pages), Manuel (42 pages), Manuel (15 pages), Manuel (42 pages)

Dell PowerEdge 2650 Manuel d'instructions
To construct the DC input power cable, perform the following steps:
Strip the insulation from the ends of the six DC power wires, exposing approximately
1
4.5 mm (0.175 inches) of copper wire.
Using a hand-crimping tool, crimp a connector contact to each DC power wire.
2
Slide a piece of heat-shrink tubing over the DC power cable.
3
The heat-shrink tubing should be approximately 3.175 cm (1.25 inches) in length.
Insert the three black –48 VDC wires into connector housing positions 2, 3, and 6 (see
4
Figure 1-1 and Table 1-1).
Insert the three red –48 VDC return wires into connector housing positions 1, 4, and 5
5
(see Figure 1-1 and Table 1-1).
Slide the heat-shrink tubing over the DC power cable so that it overlaps the connector
6
housing by at least 6.35 mm (0.25 inches).
Using a heat gun, shrink the tubing around the cable and connector housing.
7
F i g u r e 1 - 1 .
C o n n e c t o r H o u s i n g
Ta b l e 1 - 1 .
C o n n e c t o r H o u s i n g P i n A s s i g n m e n t s
Pin
Description
1
–48 VDC return
2
–48 VDC
3
–48 VDC
4
–48 VDC return
5
–48 VDC return
6
–48 VDC
front view
6
5
4
Wire Color and Size
Red 16 AWG
Black 16 AWG
Black 16 AWG
Red 16 AWG
Red 16 AWG
Black 16 AWG
3
2
1
Cabling Instr uct ions fo r t he –48 V D C
1-3