To construct the DC input power cable, perform the following steps:
Strip the insulation from the ends of the six DC power wires, exposing approximately
1
4.5 mm (0.175 inches) of copper wire.
Using a hand-crimping tool, crimp a connector contact to each DC power wire.
2
Slide a piece of heat-shrink tubing over the DC power cable.
3
The heat-shrink tubing should be approximately 3.175 cm (1.25 inches) in length.
Insert the three black –48 VDC wires into connector housing positions 2, 3, and 6 (see
4
Figure 1-1 and Table 1-1).
Insert the three red –48 VDC return wires into connector housing positions 1, 4, and 5
5
(see Figure 1-1 and Table 1-1).
Slide the heat-shrink tubing over the DC power cable so that it overlaps the connector
6
housing by at least 6.35 mm (0.25 inches).
Using a heat gun, shrink the tubing around the cable and connector housing.
7
F i g u r e 1 - 1 .
C o n n e c t o r H o u s i n g
Ta b l e 1 - 1 .
C o n n e c t o r H o u s i n g P i n A s s i g n m e n t s
Pin
Description
1
–48 VDC return
2
–48 VDC
3
–48 VDC
4
–48 VDC return
5
–48 VDC return
6
–48 VDC
front view
6
5
4
Wire Color and Size
Red 16 AWG
Black 16 AWG
Black 16 AWG
Red 16 AWG
Red 16 AWG
Black 16 AWG
3
2
1
Cabling Instr uct ions fo r t he –48 V D C
1-3