4 Parameterization
7. In the next step, you will receive a notification that the motor data identification
will be initiated with the next ON command. Confirm with OK.
This step is necessary for good control behavior. The standard behavior for the
motor identification is "Standstill". For this reason, the motor will not start up via
the IOP-2 when it is turned on for the first time via PLC or manually. The drive
will only carry out the command once the switch-on enable signal is removed
and an enable signal is given again.
Figure 4-10
8. The status screen will appear, or the diagnostic screen will appear if there are
active errors or warnings.
You can acknowledge the errors and return to the status screen by pressing
ESC.
Figure 4-11
Integration of a SINAMICS G120X frequency converter in PCS 7