6.2.4 Setup Menu

The basic commissioning procedure is shown below.
Setup Menu
1. Using the
and
2. Press
to start the basic commissioning sequence.
Reset
1. Using the
and
Inverter.
2. Press
to confirm selection.
3. The display will automatically display the next parameter in the
commissioning sequence.
The reset will be performed immediately. The reset will ensure that
all parameter values are set to their default values before applying
the new parameter values from the commissioning process.
Control mode
Sets the open and closed loop control mode of the Inverter.
1. Press
to modify the parameter value.
2. Using the
and
required control mode is displayed.
3. Press
to confirm the selected control mode.
4. The display will automatically display the next parameter in the
commissioning sequence.
The available control modes are described below.
V/f control with linear characteristics. This is the factory default.
V/f control with parabolic (quadratic) characteristics. This is used
with most Fans and Pumps due to their associated load curve.
V/f control for a parabolic (quadratic) characteristic and Energy
Control Optimization (ECO). This can be used to save energy in
non-dynamic, Fan and Pump type loads.