Siemens SINAMICS G120P VSD Manuel de démarrage - Page 23

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage pour {nom_de_la_catégorie} Siemens SINAMICS G120P VSD. Siemens SINAMICS G120P VSD 50 pages.

Siemens SINAMICS G120P VSD Manuel de démarrage
Motor data
Sets the regional settings for the motor, for example kW and Hz.
1. Press
to modify the parameter value.
2. Using the
and
required units are displayed.
3. Press
to confirm the selected value.
4. The display will automatically display the next parameter in the
commissioning sequence.
Motor voltage
The input of the voltage from the rating label of the motor must
correspond with the wiring of the motor (star/delta).
1. Press
to modify the parameter value..
2. Using the
and
decrease the displayed value.
3. Press
to confirm the selected value. The display will
automatically display the next parameter in the commissioning
sequence.
Motor current
Sets the value of the motor current in ampere taken from the motor
rating plate.
1. Press
to modify the parameter value.
2. Using the
and
decrease the displayed value.
3. Press
to confirm the selected value. The display will
automatically display the next parameter in the commissioning
sequence.
Motor power
Sets the value of the motor power in kW or hp taken from the motor
rating plate.
1. Press
to modify the parameter value.
2. Using the
and
decrease the displayed value.
3. Press
to confirm the selected value. The display will
automatically display the next parameter in the commissioning
sequence.
If P0100 = 0 or 2, data is in kW and if P0100 = 1, the data is in hp.
Page 23 of 50
keys scroll up or down the list until the
keys (or digit-by-digit method) increase or
keys (or digit-by-digit method) increase or
keys (or digit-by-digit method) increase or