ECI 1000-U LCD Manuel d'installation - Page 10

Parcourez en ligne ou téléchargez le pdf Manuel d'installation pour {nom_de_la_catégorie} ECI 1000-U LCD. ECI 1000-U LCD 18 pages.

Figure 1 - Main Menu shows the top 4 items of the main menu. Pressing the "-" button moves the
curser/hi-light down to reveal other menu options
Edit parameters – Pressing ENTER with the Edit Parameters hi-lighted will enter the parameters
menu.
Load Defaults – Pressing ENTER with Load defaults hi-lighted will load the default settings for
all parameters. See section 6.3.5.2 for default settings
Diagnostics – Pressing ENTER with Diagnostics hi-lighted will display the diagnostics screen.
See section 6.3.7 - Diagnostic Menu for more details.
Technical Support – Pressing ENTER with Technical support hi-lighted will display the
technical support screen.
Rotate screen – (Not shown above) Pressing ENTER with Rotate Screen hi-lighted will flip the
screen 180°

6.3.5 Edit parameters Menu

Figure 2 shows the top of the edit parameters menu. All parameters are listed in Section 6.3.5.2 -
Parameter settings and defaults. Pressing the "-" button moves the curser down and pressing the
"ENTER" button selects the highlighted parameter setting. Any changes occur in real time with no need
to press "ENTER". Pressing "ENTER" closes the parameter and sets the parameter at the setting in the
display. Pressing "ESC" returns to the Main Menu.
For speed and force settings, the higher the setting the fast the speed or higher the
force. For DEC the higher the setting the slower the deceleration rate.
Press "ESC" to return to main menu after all settings are complete. This saves all
changes into permanent memory. Failing to do so will result in parameters
reverting to default setting should a power loss occur.
6.3.5.1
Adjustment notes
This equipment must be installed, adjusted and maintained to conform to code requirements.
Parameters must be set to conform to kinetic energy code limitations for maximum and average kinetic
energy for ALL door/all floors (specialty or otherwise heavy doors taken into account).
Parameters must be set to conform to closing force limitations. The closing force may not exceed 135N
(30LBS). During closing, the kinetic energy may not exceed 10 joules (7.4lbs/ft)
ECI 1000-U LCD Installation Manual
ECI Model 1000N
(C) 2015 ECI, Inc.
CF cl fast sp.
CS cl slow sp.
SS cl sl. start
CFH cl fast HD
Figure 2 - Edit Parameters Menu
Electronic Controls, Inc.
7073 North Atlantic Ave. Cape Canaveral, FL 32920
800-633-9788
www.eciamerica.com
60
20
20
20
P a g e
| 10