GENERATOR START CONTROL MODULE
GSCM
APPLICATION 4 - DIESEL GENERATORS
The diesel generator is started by the GSCM in either automatic or manual mode. A field installed relay that will handle the glow
plug current is needed if not already installed on the engine. A fuel control solenoid is connected to the K3 (ignition) relay
terminals. A decompression solenoid furnished with the generator must be wired to K4 (shutdown) relay to energize on shutdown.
APPLICATION 5 - AUTOMATIC GENERATOR POWERED AC PUMP
In this application the GSCM is connected to a pressure or level switch into the battery sense terminals. See Section-3:9 for
making the appropriate cut-in and cut-out adjustments. The cut-in and cut-out adjustments must be set at the maximum for the
switched input auto start mode to operate (see Sections 3:9 & 4:9). The K5 (load) relay energizes the pump contactor.