6 Terminals
6.1 TYPE
The PCB terminal connector is a Phoenix Contact style with 5.08mm pitch. Austdac
supplies the module with either a 90˚ free hanging push-in spring terminal plug.
6.2 LAYOUT
6.2.1 Termination Connection
If system termination is determined to be required, HubBus signal shall be
connected to the "Term 1" terminals; if no system termination is required, HubBus
signal shall be connected to the "No Term" terminals. "Term 2" and "Term 3"
terminals are not currently used but are provided for future development only.
WARNING:
The HubBus Signal –ve line must not be tied to any common, 0V, ground or
Earth points.
HubBus Line Termination Unit
HBLTU USER MANUAL
Figure 3: Terminal Plug
HBLTU
5
Sig +
6
Sig -
7
Sig +
8
Sig -
Table 1: HBLTU Terminals
11 OF 12
Sig +
1
Sig -
2
Sig +
3
Sig -
4
125-258-12
Issue: 01