GAPOSA QC101 Manual Petunjuk Pengoperasian - Halaman 14
Jelajahi secara online atau unduh pdf Manual Petunjuk Pengoperasian untuk Unit Kontrol GAPOSA QC101. GAPOSA QC101 16 halaman. Single-phase control unit
RESET
Through the reset procedure:
• all memorised transmitters will be deleted
• the programming of pause time and of the stroke are reset to default
conditions (working time of 30 seconds, automatic closing disabled).
• the "Emergency mode with faulty bar" is also turned off.
During the reset procedure, all controls are inhibited.
To reset the control unit, you must:
1. Place all DIP in OFF
2. Place DIP 5 and 6 in ON
3. The green LED will switch off while the red one will start flashing
rapidly. After the reset, the red LED switches off while the green LED
will start making three quick flashes every 3 seconds.
4. Place DIP 5 and 6 in OFF. The green LED will remain ON and steady and
the reset procedure is completed.
5. You can now reposition the DIP according to the desired functions.