AXITEC AXIhycon 5H Panduan Memulai Cepat - Halaman 3

Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Inverter AXITEC AXIhycon 5H. AXITEC AXIhycon 5H 8 halaman.

4.
CONNECTING THE SMART METER
Install the smart meter for communication.
CAUTION:
Ensure that the AC cable is completely disconnected from the power source
before connecting the smart meter, EMS, and CT clamps.
NOTE:
Please ensure that the alignment of the current trans-
former (CT clamps) is correct, as otherwise the system
will not function properly.
NOTE:
The pin configuration of the meter port (at the inverter)
follows the EIA/TIA 568B standard.
RS485A on Pin 1: Orange/White
RS485B on Pin 2: Orange
NOTE:
The pin configuration of the Smart Meter for RS485 is as follows:
RS485A is connected to pin 14.
RS485B is connected to pin 13.
AXIhycon-EN231024
RS485B
RS485A
2