ABB Jocab Safety Vital 2 Petunjuk Pengoperasian - Halaman 4
Jelajahi secara online atau unduh pdf Petunjuk Pengoperasian untuk Pengontrol ABB Jocab Safety Vital 2. ABB Jocab Safety Vital 2 11 halaman. Safety controller
Juga untuk ABB Jocab Safety Vital 2: Manual (14 halaman)
Time delay
Output group 2 can be off-delayed by connecting the inputs 0.5s and 1.0s to +24V. The system is
binary so connection of one of these inputs adds the corresponding time.
Connecting 0.5s = 0.5 sec. delay
Connecting 1.0s = 1.0 sec. delay
Connecting both 0.5s and 1.0s = 1.5 sec. delay
Mode selection
Both Vital 2 and Vital 3 can be set to work in one of the three modes M1, M2 or M3. Selection of
mode is done by connecting one of the terminals marked M1, M2 or M3 to +24V.
The following pictures show the logic for each mode of operation.
4
Vital2&3_Manual_v1D
www.jokabsafety.com