Juga untuk Siemens SINAMICS S120: Panduan Pengoperasian (20 halaman), Memulai (32 halaman), Manual (41 halaman), Deskripsi Singkat (22 halaman), Instruksi Untuk Pemasangan Di Kabinet Untuk Aplikasi Drive Kelautan (28 halaman), Manual Aplikasi (34 halaman), Manual Aplikasi (46 halaman), Panduan Petunjuk Pengoperasian (22 halaman), Memulai (32 halaman), Panduan Petunjuk Pengoperasian (21 halaman), Manual Teknik (30 halaman), Panduan Komisioning (20 halaman)

Siemens SINAMICS S120 Manual
SINAMICS S120 Fail-Safe Drives
5

Overview and operator control

5.1

Description of the operator control

Hardware overview
The Emergency Stop pushbutton –S3 is released to power-up the system.
The safety function SS1 is de-selected at both drives using reset button –
S4 via output F-DO 0 of the F-CPU; pulse cancellation at the drives is with-
drawn. The drives can then be moved (operated) using the knob-operated
switch –S6.
When safety door 1 is closed (knob-operated switch -S1, ON switch posi-
tion), drive 1 rotates with n=800 rpm. If safety door 1 (switch –S1) is
opened, the data set is changed-over in drive 1 and for drive 1 the setpoint
speed is n=20 rpm. When switch -S1 is opened, the SLS safety function in
drive 1 is activated. By closing safety door 1, a speed of n=800 rpm is again
entered (speed setpoint). Drive 2 is not influenced.
If safety door 2 is closed (knob-operated switch –S2, switch position ON)
then a setpoint speed of n=333 rpm is entered for drive 2. If safety door 2
(switch –S2) is opened, then drive 2 has a speed setpoint of n=33 rpm as
the data set is changed-over. When switch –S2 is open, the SLS safety
function in drive 2 is activated. By closing safety door 2, a speed setpoint of
n=333 rpm is again entered. Also in this case, drive 1 is not influenced.
If safety door 1 (knob-operated switch –S1, center position) is opened, then
the SLS function is activated for drive 1. Drive 2 is not influenced. When
opening safety door 2 (knob-operated switch -S2, center position) the SLS
function for drive 2 is activated.
I DT Safety Integrated
Page 17/43
Entry ID: 28424136
MC-FE-I-005-V11-EN