8 .2 Electrical Connections
For modules connected in series, only modules of the
same amperage rating may be used together. For
modules connected in parallel, modules with the same
voltage ranges must be used together. The modules
must not be operated at a higher voltage than the
permissible system voltage.
8 .3 Junction box
Avoid standing water in the junction box area.
When mounting horizantally, make sure that the
junction boxes are facing upwards.
The junction boxes and the surrounding area (at least
15 mm from the glass edge inwards and at least 25
mm to the left and right of the junction box) must
be protected against direct sunlight, precipitation
and dirt.
The use of an aluminum clamping rail is recommended
for this purpose.
8 .4 Cable couplers for junction boxes
Only use cable couplers that are the same type and
compatible to the specific junction box.
Insert the cable couplers in the junction boxes only
through the outer slots on the left and on the right
of the module, as shown in the picture.
Figure 8D
8 .5 Connectors
Incompatible or unsuitable connectors can overheat.
Fire hazard!
Only use connectors that are the same type and
compatible to the specific inverter.
This module type can be fitted with the following
connectors:
TE - SOLARLOK Slim Line (Plus:1-1987559-1; Minus:
1-1987559-2)
You can remove the connector on a module and repla-
ce it with another connector, if necessary. You retain
aleo solar GmbH | Marius-Eriksen-Straße 1 | 17291 Prenzlau | Germany | [email protected]
Installation Manual GG Elegante Rel. 1.5, 01/2022, EN
Copyright © 2021 aleo solar GmbH