Aleo ELEGANTE 설치 매뉴얼 - 페이지 9

{카테고리_이름} Aleo ELEGANTE에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Aleo ELEGANTE 16 페이지. Bipv modules
Aleo ELEGANTE에 대해서도 마찬가지입니다: 설치 매뉴얼 (14 페이지)

8 .2 Electrical Connections

For modules connected in series, only modules of the
same amperage rating may be used together. For
modules connected in parallel, modules with the same
voltage ranges must be used together. The modules
must not be operated at a higher voltage than the
permissible system voltage.

8 .3 Junction box

Avoid standing water in the junction box area.
When mounting horizantally, make sure that the
junction boxes are facing upwards.
The junction boxes and the surrounding area (at least
15 mm from the glass edge inwards and at least 25
mm to the left and right of the junction box) must
be protected against direct sunlight, precipitation
and dirt.
The use of an aluminum clamping rail is recommended
for this purpose.

8 .4 Cable couplers for junction boxes

Only use cable couplers that are the same type and
compatible to the specific junction box.
Insert the cable couplers in the junction boxes only
through the outer slots on the left and on the right
of the module, as shown in the picture.
Figure 8D

8 .5 Connectors

Incompatible or unsuitable connectors can overheat.
Fire hazard!
Only use connectors that are the same type and
compatible to the specific inverter.
This module type can be fitted with the following
connectors:
TE - SOLARLOK Slim Line (Plus:1-1987559-1; Minus:
1-1987559-2)
You can remove the connector on a module and repla-
ce it with another connector, if necessary. You retain
aleo solar GmbH | Marius-Eriksen-Straße 1 | 17291 Prenzlau | Germany | [email protected]
Installation Manual GG Elegante Rel. 1.5, 01/2022, EN
Copyright © 2021 aleo solar GmbH
8A
8B
8C
9