DSEG8660 Installation Instructions
This document details the installation and operation requirements of the
DSEG8660 module and is part of the DSEGenset® range of products.
The DSEG8660 module contains two software applications, Mains
Controller and Group Controller.
The DSEG8660 module has been designed to monitor the mains (utility)
supply and automatically start/stop one or more generator sets equipped
with DSEG8600 (Multi Set) controllers depending upon the status of the
mains (utility) supply.
Configured as a Group Controller which allows the expansion of a system
beyond the 64-module limit that is imposed by the capacity of a CAN bus.
CONTROL BUTTONS
Icon
Description
Mode Button
In the G8660 the mode button is used to select Auto Mode,
DE
Test Mode, or Manual Mode. Pressing the button cycles
through Auto mode > (Test mode) > Manual mode > Auto
mode >.
Alarm Mute / Lamp Test
This button silences the audible alarm in the controller, de-
activates the Audible Alarm output (if configured) and
illuminates all the LEDs on the module's facia as a lamp test
function.
RHS Breaker Button
Transfer to generator / bus
LHS Breaker Button
Transfer to Mains
Stop / Reset Mode
This button places the module into its Stop/Reset Mode.
This clears any alarm conditions for which the triggering
criteria has been removed.
If the generators are running and the module is put into
Stop/Reset Mode, the module automatically instructs the
generators to ramp off load and stop.
Should any form of start signal be present when in
Stop/Reset Mode the generators remain at rest.
Start
This button is only active in the Stop/Reset Mode and
Manual Mode
Pressing the Start button in Stop/Reset Mode starts the
generators and runs them off load.
Pressing the Start button in Manual Mode starts the
generators and runs them off load in.
Menu Navigation
Used for navigating the instrumentation, event log and
configuration screens.
ACCESSING THE MAIN CONFIGURATION EDITOR
053-253
•
Ensure the generator bus is dead and the module is in STOP mode
ISSUE 1
by pressing the (Stop/Reset) button.
•
Navigate to Editor page:
Press
Home
Page
Once selected, the page remains on the LCD display until the user selects a different
page, or after an extended period of inactivity (LCD Page Timer), the module reverts
to the home display.
•
Press the Tick
correct value.
•
Press the Next Page
shows as '#' for security.
•
Repeat this process for the other digits of the PIN number. Press the Previous Page
back to adjust one of the previous digits.
•
When the Tick
number is not correct, the PIN must be re-entered.
•
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed:
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the Next Page or Previous Page
•
Press the Scroll
•
To edit the parameter, press the Tick
editing.
•
Press the Scroll
required value.
•
Press the Tick
saved.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to
ensure security. The PIN number is automatically reset when the editor is exited (manually or automatically) to
ensure security. Comprehensive module configuration is possible using the DSE Configuration Suite PC
Software, refer to DSEpublication 057-322 DSE8600 Configuration Suite PC Software Manual available from
www.deepseaelectronics.com.
Navigate
Press
Main
Editor
Page
Page
button, the first '#' changes to '0'. Press the Scroll
button when the first digit is correctly entered. The digit previously entered now
button is pressed after editing the final PIN digit, the PIN is checked for validity. If the
buttons to cycle to the section to view/change.
buttons to select the parameter to view/change within the currently selected section.
button to enter edit mode. The parameter is highlighted to indicate
buttons or Next Page or Previous Page
button to save the value. The parameter ceases flashing to indicate that it has been
buttons to adjust it to the
button to move
buttons to change the parameter to the