Sfoglia online o scarica il pdf Istruzioni per l'installazione per Controllore DSE DSEG8660. DSE DSEG8660 5.
DIMENSIONS AND MOUNTING
Parameter
Specification
248 mm x 182.6 mm x 45.2 mm (9.76 " x 7.18 " x 1.77 ")
Dimensions
220 mm X 160 mm (8.7" X 6.3")
Panel Cutout
Weight
0.76 kg (1.67 lb)
Operating Temperature with
-30 ºC to +70 ºC (-22 ºF to +158 ºF)
Standard Display
Operating Temperature with
-40 ºC to +70 ºC (-40 ºF to +158 ºF)
Heated Display
Storage Temperature
-40 ºC to +80 ºC (-40 ºF to +176 ºF)
FIXING CLIPS
NOTE: In conditions of excessive vibration, mount the control panel on suitable anti-vibration mountings
The module is held into the control panel fascia using the supplied fixing clips.
•
Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip.
•
Insert the three 'prongs' of the fixing clip into the slots in the side of the DSE module's case.
•
Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are inside
their allotted slots.
•
Turn the fixing clip screws clockwise until they make contact with the panel fascia.
•
Turn the screws a quarter of a turn to secure the module into the control panel's fascia. Care must be taken
not to over tighten the fixing clip screws.
TYPICAL WIRING DIAGRAMS
NOTE: A larger version of the Typical Wiring Diagram is available in the product's operator
manual, refer to DSE Publication: 057-323 DSE8660 Operator Manual available from
www.deepseaelectronics.com for more information.
Mains Parallel Controller