ACCESSING THE 'RUNNING' CONFIGURATION EDITOR

Press the Next Page
button to access the Main Menu page.
Press the Previous Page
button followed by either the Scroll
buttons to locate the 'Running' Configuration Editor.
Next Page or Previous Page
RUNNING CONFIGURATION EDITOR PARAMETERS
Section
Parameter As Shown On Display
Display
Contrast
Units Pressure
)
Units Temperature
Units Volume
Language
Synchronising Commissioning Screen
Override Starting Alarms
Voltage Adjust
(Manual Mode Only With Gen Open)
Frequency Adjust
(Manual Mode Only With Gen Open)
Load Control
Injection Port
Mains Decoupling Test Mode
Power Control Mode
Load Parallel Power
Load Parallel kVArs
Load Parallel PF
Governor Droop Offset
Governor Ramp Rate
AVR Droop Offset
AVR Ramp Rate
Load Priority
buttons or the
Values
75 %
kPa, bar, psi
°C, ° F
Litres. Imp gal. Us gal
English, Other
Active / Inactive
Active / Inactive
0%
0%
Active / Inactive
Active / Inactive
Constant Power / Frequency-Power / Voltage-
Power
0 %
0 %
0.00 pf
0%
0%
0%
0%
1-64

ELECTRICAL SPECIFICATIONS

Parameter
DC Supply Voltage
Maximum Operating Current
Maximum Standby Current
Typical Power
(Controller On, Heater Off)
Typical Power
(Controller On, Heater On)
Mains Phase to Neutral Voltage Sensing
Mains Phase to Phase Voltage Sensing
Mains Voltage Sensing Offset from Earth
Volt-Free Output Rating

REQUIREMENTS FOR UL CERTIFICATION

WARNING!: More than one live circuit exists, see diagram overleaf for further information.
Specification
Description
Screw Terminal Tightening
• 4.5 lb-in (0.5 Nm)
Torque
• Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to
Conductors
2.5 mm²).
• Conductor protection must be provided in accordance with NFPA 70, Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine starting battery
or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors shall be
separated and secured to maintain at least ¼" (6 mm) separation from the generator
and mains connected circuit conductors unless all conductors are rated 600 V or
greater.
• Must be connected through UL Listed or recognized isolating current transformers
Current Inputs
with the secondary rating of 5 A max.
• Must be connected to communication circuits of UL Listed equipment
Communication Circuits
• 0.5 A
DC Output Pilot Duty
• Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding
Mounting
air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs do not
exceed 300 V. When used to monitor voltages over 300 V device to be installed in
an unventilated or filtered ventilation enclosure to maintain a pollution degree 2
environment.
Maximum Operating
• 122 ºF (50 ºC)
Temperature
Specification
8 V
to 35 V
DC
DC
530 mA at 12 V
280 mA at 24 V
320 mA at 12 V
120 mA at 24 V
3.8 W to 4.1 W
6.8 W to 7.1 W
15 V
to 345 V
AC
AC
26 V
to 720 V
AC
AC
100 V
AC
8 A at 250 V
5 A at 30 V
AC,
DC