Connector mounting

5. Connector mounting
Strip approx. 35 mm of the cable and remove approx. 5 mm insulation from each wire
end.
Loosen the screw 1.
Lever the terminal holder 5 out of the enclosure 2 using the mounting hole on the seal
6.
Unscrew the cable fitting 4 and take out the cable seal 3.
Lead the cable through the cable fitting 4 and the cable seal 3 in the enclosure 2.
Inproper mounting.
NOTICE
Enclosure seal can become damaged.
Do not push the terminal holder 5 out using the screw hole or the cable fitting 4.
Unscrew the cable fitting 4 and take out the cable seal 3.
Lead the cable through the cable fitting 4 and the cable seal 3 in the enclosure 2.
Connect the cable ends in accordance with the wiring diagram (Fig. 4.1).
Loosen the screw terminals of the terminal holder 5, connect the stripped wire ends in
accordance with the wiring diagram (Fig. 4.1) and screw the screw terminals in tight.
Put the terminal holder 5 and snap the connector seal 6 in the enclosure 2.
When screwing the cable fitting 4, make sure the cable fitting 4 with the cable seal
are assembled correctly and the cable seal 3 is not damaged.
Plug the socket (2+5+6) to the contacts 7.
Tighten the screw 1.