Dimensional drawing
Specification
W1 Width
D1 Depth
H1 Height
Electrical single phase
Electrical three phase
Minimum circuit ampacity
Minimum overcurrent protection
Electrical
208‑230 V/60/3 ‑ three phase
Cooling unit operating limits
(air temperature)
Maximum refrigerant line run length
Maximum line rise above evaporator
Evaporator mounting above condenser
Maximum refrigeration line drop
BTU/hr (Kcal/hr) at
0 F (‑18 C) evaporator, 90 F (32 C) ambient air, 1650N units only)
Rack systems * EPR valve ‑ set to
Approximate ship weight
NOTE:
1. 1650 model condensing units have a liquid suction line heat exchanger. The entire liquid line should be insulated separately from
the suction line.
2. Outdoor installation of low side is not recommended and will void warranty.
* EPR valve to be supplied by installer.
Remote 1650 series ice machine
D1
W1
36.25" (92.0 cm) – all models
25.50" (64.8 cm) – all models
26.10" (66.3 cm) – all models
208‑230/60/1
208‑230/60/3
single phase 29.90 A
three phase 21.24 A
single phase 50 A
three phase 35 A
35 amps, requires dedicated
amp circuit, internal connection
min ‑20 F (‑29 C)
max 120 F (49 C)
100' (30.5 m)
35' (10.7 m)
15' (4.6 m)
15' (4.6 m)
13,000 (3,276)
0 F (‑18 C)
340 lb (154 kg)
H1
3
Form# 7040