1.5
If using three-conductor cable, stagger leads approximately 6" (150 mm), 9"
(230 mm), and 12" (305 mm) from end of split. Cut corresponding conductors
to match.
Scuff &
Clean
4"
(100 mm)
1.6
Remove jacket and phase insulation for one-half butt connector length or two
parallel connector lengths from each phase end.
1.7
Taper jacket approximately 1" (25 mm). Taper or bevel ends of insulation to
conductor.
1.8
Scuff and clean 4" (100 mm) of cable jacket beyond each taper or split end.
1.9
Cut ground and ground check conductor to lie in between connections of phases.
2.0

Install Connectors

2.1
Join conductors one at a time using proper connectors (butt, parallel or modified
crow's foot) and crimping tool.
Note: Insulate each conductor in sequence before connecting the next conductor,
ground, or ground check.
78-8127-6830-3-C
9"
(230 mm)
6"
(150 mm)
1" (25 mm)
taper
Figure 3
Figure 4
3
12"
(305 mm)
Required Connector Length