5 Connecting to power supply
Electronics and connec-
tion compartment
18
3
Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) of insulation from the ends of the individual wires
4
Insert the cable into the sensor through the cable entry
5
Open the terminals with a screwdriver
6
Insert the wire ends into the open terminals according to the wiring
plan
7
Tighten the terminals with a screwdriver
8
Check the hold of the wires in the terminals by lightly pulling on
them
9
Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10 Screw the housing cover on
The electrical connection is finished.

5.3 Wiring plan, single chamber housing

The following illustrations apply to the non-Ex as well as to the EEx-d
version.
5
Fig. 10: Electronics and connection compartment, single chamber housing
1
Control lamp
2
DIL switch for mode adjustment
3
DIL switch for switching point adaptation
4
Ground terminal
5
Connection terminals