SPECIFIC CONDITIONS OF USE
SPECIFIC CONDITIONS OF USE
SPECIFIC CONDITIONS OF USE
INSTALLATION / SET-UP
The units must be installed, connected and set up by qualified staff. The qualified staff must have knowledge of protection classes,
regulations and provisions for apparatus in hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable for the application.
INSTALLATION REMARKS / INSTALLATION
Make sure only qualified personnel performs the installation/maintenance/service.
Before removing the sensor, or before connecting or disconnecting the wiring, turn off the power supply. Do not
disconnect, unless the area is non-explosive.
Verify that the environmental temperature is within the temperature class required for the area.
•
Ambient temperature range is -30 °C to +50 °C.
•
Never remove the trimmer cover protector unless the area is non-explosive.
•
Adhere to the relevant national regulations and provisions.
•
The relevant installation regulations must be adhered to. In particular, take into account the requirements relating
to the temperature limitation as regards the expected dust deposits.
•
Avoid electrostatic charging on housings and cables
•
In case of cleaning the sensor, this must be done with a damp cloth, in order to prevent build-up of electrostatic
charges.
•
If fast moving particles are present a physical barrier shall protect the sensor.
•
Cable shall be protected from pulling or twisting.
•
The sensor may only be connected/supplied from a circuit having a prospective short circuit current of not
greater than 10kA.
•
The sensor must be protected against exposure to direct sunlight and other ultraviolet light sources.
•
The sensor is manufactured with a permanently mounted cable gland and permanently connected cable that is
non-replaceable and shall be terminated in a safe area or in a suitable certified termination box.
•
If the user reduces the sensitivity to almost minimum, the sensor will not be able to detect objects in front of it. In
this fail situation, the internal relay will always be ON but the temperature class 85