Clearing Troubles
[4]
Failure to Communicate
Panel unable to send information to
central station. Check telephone
line, telephone number of Central
Station, format and reporting
codes. Dial number from handset
and listen for tones to ensure
number correct.
[5]
Zone Fault
The trouble will be indicated if any
zone on the system is in a trouble
condition, i.e. if it could not send
an alarm to the panel if required to
do so. Press [5] to view the zone
number.
[6]
Zone Tamper
This condition will only be gener-
ated for zones with DEOL resistor
supervision. This trouble is gener-
ated when a tamper is present.
Press [6] whilst in trouble mode to
view zone with a tamper condition.
[7]
Device Low Battery
Generated when a wireless device
exhibits a low battery. Press [7]
again to view which devices have
low battery.
[8]
Loss of System Time
This condition occurs when the
control unit is powered up and the
internal clock has not been set up.
[*][6][Master Code][1] to put in new
date and time.
22
Clearing Troubles

Power Up

Initial Start Up

Before turning on the mains power,
make sure that all electrical connec-
tions are completed and all devices
are connected correctly to the main
PCB. The two YELLOW leads on the
transformer should be securely
terminated in the two terminals
marked AC.
Before turning ON the mains power,
ensure you have the battery con-
nected to the control panel, then
insert the fuse into the terminal block
using the holder provided.
The control panel keypad will beep on
power up and the LCD version shows
the software version on the screen.
This is normal.
The Keybus voltage should read 12.0
volts to 13.8 volts in the normal state.
If a low Keybus error occurs, the
reading should be around 11.0 volts
to 11.5 volts. A critical condition on
the Keybus is anything between 10.0
volts and 10.3 volts. This will result in
a shutdown.
If you have a Keybus problem, you
should carry out the following: check
the connections on all Keybus-
connected devices; check the cable
run distance; check that cable type is