6 SPECIFICATION

Cranking Dropouts:
Alternator Input Range:
Mains Input Range
Alternator Input Frequency:
Mains Input Frequency
Auxiliary Outputs:
Operating Temperature Range:
Applicable Standards
Deep Sea Electronics plc reserve the right to change specification without notice.
- 10 -
057-043 705 Operating Instructions Issue 1.1 18/06/2007
705 ATS controller operators manual
DC Supply:
8 Volts to 35 Volts DC Continuous.
Able to survive 0 Volts for 50 mS, providing supply was at
least 10 V before dropout and supply recovers to 5 Volts.
This is achieved without the need for internal batteries.
Max. Current:
Operating 50mA
Standby 10mA
75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%)
15 – 277 Volts (ph-N) AC (+20%)
50 - 60 Hz at rated engine speed
(Minimum: 75V AC Ph-N)
Generator available 45Hz
Generator failed 20Hz
50 – 60 Hz
Start Output:
1.2 Amp DC at supply voltage.
Fuel Output:
1.2 Amp DC at supply voltage.
1.2 Amp DC at supply voltage.
Dimensions:
125mm x 165mm x 28 mm
Charge Fail:
12 Volts = 8 Volts CF 24 Volts = 16 Volts CF
-30°C to + 70
Compliant with BS EN 60950 Low Voltage Directive
Compliant with BS EN 50081-2: 1992 EMC Directive
Compliant with BS EN 61000-6-4: 2000 EMC Directive
Compliance to European Legislation
Registered Component for USA & Canada
0
C
JR