DSE DSE705 운영 매뉴얼 - 페이지 8
{카테고리_이름} DSE DSE705에 대한 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DSE DSE705 13 페이지. Ats control module
Function
Remote Start
Function
The remote start input can be configured to one of the following.
♦
Remote start is off load – The generator will start and run off load when the remote start input is active.
♦
Remote start is on load – The generator will start, and the load transferred to the generator when the remote start
is active.
Auxiliary Output 1
Function
Programmable output can be configured to one of the following.
♦
Mains Failure. - The output is energised after the delay mains fail timer has elapsed and stays energised until the
delay mains return timer has elapsed.
♦
Generator Available. - The output is energised after the warm up timer has elapsed and generator voltage is
sensed.
♦
Generator On Load. - The output is energised when the unit has switched over to generator supply.
♦
Mains On Load. - The output is energised when the unit has switched over to mains supply.
♦
System in auto. - The output is energised when the unit is in automatic mode.
♦
Close to Neutral Position. - The output is energised when the close to neutral position input is active.
Auxiliary Output 2
Function
Programmable output can be configured to one of the following.
♦
Mains Failure. - The output is energised after the delay mains fail timer has elapsed and stays energised until the
delay mains return timer has elapsed.
♦
Generator Available. - The output is energised after the warm up timer has elapsed and generator voltage is
sensed.
♦
Generator On Load. - The output is energised when the unit has switched over to generator supply.
♦
Mains On Load. - The output is energised when the unit has switched over to mains supply.
♦
System in auto. - The output is energised when the unit is in automatic mode.
♦
Close to Neutral Position. - The output is energised when the close to neutral position input is active.
Mains Under
Voltage
(Trip / Return)
If for example 180V/200V is selected the generator will be started and the load transferred if any phase falls below
180V with respect to the neutral for the duration of the delay start timer. The load will be transferred back to mains
when the mains voltage returns to 200V or higher for the duration of the mains return timer. (The system must be in
Auto)
- 8 -
057-043 705 Operating Instructions Issue 1.1 18/06/2007
705 ATS controller operators manual
FUNCTIONS AND CONFIGURATION TABLE
Value (Default in Bold)
Remote Start Is Off load
Remote Start Is On
Load
Not used
Mains Failure
Generator Available
Generator On Load
Mains On Load
System in Auto
Close to neutral Position
Not used
Mains Failure
Generator Available
Generator On Load
Mains On Load
System in Auto
Close to neutral Position
60V / 70V
70V / 80V
80V / 90V
90V / 100V
120V / 140V
140V / 160V
160V / 180V
180V /200V