7. Programming
7.1. Single Anyscene 512
As supplied, the Anyscene 512 scene memories have a range of saved presets allowing
electrical contractors to confirm correct operation before final commissioning of the
system. They can be easily programmed from any source of DMX data including another
Anytronics scene memory, DMX lighting desk or a computerised lighting system.
Anyscene 512 should be programmed whilst connected into the final installation and the
programming source should be connected into the system.
a) Turn the MWP DIL switch to 'OFF'
b) Connect the DMX programming source (DMX Desk etc.) into the system
c) Power the DMX programming source
d) Power the Anyscene 512, the power and yellow data LED should be lit
e) Use the DMX programming source to adjust the required channels
f) Press and hold the button on the Anyscene 512 where the current scene should
be saved
g) The Anyscene 512 data LED will flash twice to show the data has been saved.
h) Repeat e) to g) for all required scenes
i)
Once all scenes have bee saved turn the MWP DILL 'ON' to protect the recently
programmed scenes
Note: To access scenes 8 to 15 the down button should be held before the scene number
is pressed. To access scenes 16 to 22 the up button should be held before the scene
number is pressed.
Note: that unless the data LED is illuminated, and unless the internal MWP DIL switch is
in the OFF position, no programming of the scenes will be possible.
7.2. Multiple Anyscene 512
When programming a multi Anyscene 512 installation each unit should be connected into
the system individually and then programmed using the sequence of 7.1.
If all Anyscene 512 are to be programmed the same the following procedure should be
followed,
a) Program the
b) Keep the
first unit
c) Ensure the MWP of the
d) Recall the required scene on the
e) Press and hold the required scene location on the
f) The data LED on the
g) Repeat d) to f) for all scenes
h) Remove the
to 'ON'
i)
Repeat b) to h) for all subsequent Anyscene 512
Units 5 & 6 Hillside Industrial Estate
London Road, Horndean,
Hampshire, PO8 0BL
Tel +44 (0)23 9259 9410
Fax +44(0)23 9259 8723
first unit
as per section 7.1
powered and then insert the
second unit
first unit
second unit
second unit
from the system and turn MWP DIL switch for that unit
Page 10 of 13
second unit
is off
second unit
should flash twice
Anyscene 512 Operating
The
into the system
AT1039 Issue 1
Instructions