Danfoss VLT 5000 매뉴얼 - 페이지 5
{카테고리_이름} Danfoss VLT 5000에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Danfoss VLT 5000 7 페이지. Frequency converter
Danfoss VLT 5000에 대해서도 마찬가지입니다: 애플리케이션 노트 (16 페이지)
PCP communication
Via the CMD tool you are able to read and write to
parameters and read the English parameter text of
each parameter.
To start PCP communication you must be in Monitor
state. Click on the station number and click on the
right mouse button and choose Device
Parametization.
The dialog box will now show Danfoss, VLT 5000,
Profile: 21. In order to be able to read in all
parameters in the VLT frequency converter select
Device and Read Parameter List. The CMD tool will
now start reading all parameters, this will take 3-4
minutes.
When all parameters have been read, CMD will
show the first parameter 55F1 Hex Language at the
first row.
55F1 Hex corresponds to 22001
all VLT 5000 parameters simply can be accessed by
adding 22000
to the VLT 5000 parameter. For
D
example if you want to write to parameter 207
Ramp up time 1 you must write to 22207
Hex).
The CMD tool can only indicate parameters by
hexadecimal numbers.
MN.50.U1.02 - VLT is a registered Danfoss trademark
VLT
If you want to change the value of parameter 207
Ramp up time 1 to 10 sec you must write 1000 in
column next to index 56BF Hex. You have to
enter 1000 because VLT parameter 207 has a
conversion index of -2 = 10
Highlight the row by clicking on 60 and click on F5
Write Value. The ramp up time in parameter 207
has now been changed to 10 sec.
At the bottom of the parameter list the Interbus
Drivecom 21 objects are available. These objects
are not accessible via the LCP but only via Interbus
PCP communication.
Please have a look at the Interbus operating
instructions for further description of these objects.
. This means that
D
(56BF
D
®
5000 and Interbus CMD
-2
.
5