TO ENTER PROGRAMMING MODE:

Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
A. POWER UP, then depress [ ] and [#] both at once, within 50 seconds of powering up )if
must be used to reenter program mode). OR
B. Initially, key: Installer Code (4 + 1 + 1 + 2) plus 8 + 0 + 0.
Data Field Programming Procedures
Task
Procedure
Press [ ∗ ] + [Field Number], followed by the required entry.
Go to a Data Field
Entering Data
When the desired field number appears, simply make the required entry. When the last entry for a field is entered,
the keypad beeps three times and automatically displays the next data field in sequence.
If the number of digits that you need to enter in a data field is less than the maximum digits available (for example,
the phone number fields *41, *42), enter the desired data, then press [ ∗ ] to end the entry. The next data field is
displayed.
Review a Data Field
Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Press [ ∗ ] + [Field Number] + [ ∗ ]. (Applies only to fields ∗ 40–*46, *94, and pager programming fields)
Deleting an Entry
Interactive Menu Mode Programming (∗56, ∗57, ∗58, ∗79, ∗80, ∗81, ∗82)
See respective sections in this document for programming procedures.
Press [ ] + [Interactive Mode No.] (for example, 56). The alpha display keypad will display the first of a series of prompts.
Interactive Menu Mode
56 Zone Programming
57 Function Key Programming
58 Zone Programming
(Expert mode)
79 Output Device Mapping
80 Output Programming
81 Zone List Programming
82 Alpha Programming
INITIALIZE DOWNLOAD and RESET DEFAULTS
96 Initializes download ID and subscriber account number.
97 Sets all data fields to original factory default values.
TO EXIT PROGRAMMING MODE:
98 Exits programming mode and prevents re-entry by: Installer Code + 8 + 0 + 0. If 98 is used to exit programming mode,
system must be powered down, and method A above used to enter the programming mode.
See field *88 for other *98 Program mode lockout options.
99 Exits programming mode and allows re-entry by: Installer Code + 8 + 0 + 0 or method A above.
Special Messages
OC = OPEN CIRCUIT (no communication between Keypad and Control).
EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds. This will revert to
a "Ready" message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this delay by pressing [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after you correct the
programming.
Table of Device Addresses
This Device
RF Receiver
Long Range Radio
4286 Voice Module
4204 Relay Module
Keypads:
keypad 1
keypad 2
keypad 3
keypad 4
keypad 5
keypad 6
keypad 7
keypad 8
5800TM Module
†† Addressable devices are identified by "1" plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
Used to Program
Zone characteristics, report codes, alpha descriptors, and serial numbers for RF trans.
Unlabeled keypad keys (known as ABCD keys) for special functions
Same options as *56 mode, but with fewer prompts. Intended for those familiar with
this type of programming, otherwise *56 mode is recommended.
Assign module addresses and map individual relays/powerline carrier devices
4204 Relay modules, Powerline Carrier devices, or on-board triggers
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Zone alpha descriptors
††
Uses Address Reports as
00
100
03
103
04
104
12
112
16
n/a
17
n/a
18
n/a
19
n/a
20
n/a
21
n/a
22
n/a
23
n/a
28
n/a
– 2 –
98 was used to exit previously, this method
Enabled By...
*56 zone programming: input device type entry
automatic if output to long range radio field *29 enabled
automatic if phone module access code field *28 enabled
*79 output device programming: entered at device address prompt:
data field programming as listed below:
always enabled, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
automatic