∗49
Split/Dual Reporting
0 = Standard/Backup reporting only (all to primary unless fail)
Primary Phone No.
1 = Alarms, Restore, Cancel
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel
4 = All except Open/Close, Test All
5 = All
∗50
Burglary Dialer Delay
0 = no delay UL: must be "0"
1 = 15 seconds
2 = 30 seconds
3 = 45 seconds
∗53
SESCOA/Radionics Select
0 = Radionics (0-9, B-F), and all formats other than SESCOA
1 = SESCOA (0-9 only reporting)
∗54
Dynamic Signaling Delay
Delay selectable from 0 to 225 secs in 15-sec increments.
0 = no delay (both signals sent),
1 = 15 secs,
2 = 30 secs, etc
UL: Grade AA must be "0;" Grade A must be "15" max
∗55
Dynamic Signaling Priority
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a DACT
and LRR, this field must be "0".
∗56 -*58
Menu Modes (see page 2 for description)
PROGRAMMING SYSTEM STATUS, & RESTORE REPORT
CODES ( 59 – 76, & 89):
For 3+1 or 4+1 Standard Format: Enter a code in the first box: 1–
9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15
for F.
A 0 ( not #+10) in the first box will disable a report. A 0 ( not #+10) in
the second box will result in automatic advance to the next field.
For Expanded or 4+2 Format: Enter codes in both boxes (1st and
2nd digits) for 1–9, 0, or B–F, as described above.
A 0 ( not #+10) in the second box will eliminate the expanded
message for that report. A 0 ( not #+10) in both boxes will disable
the report.
For Ademco Contact ID® Reporting: Enter any digit (other than 0)
in the first box, to enable zone to report (entries in the second boxes
are ignored).
A 0 ( not #+10) in the first box disables the report.
UL: see installation instructions for requirements
SYSTEM STATUS REPORT CODES
∗59
Exit Error Report Code
∗60
Trouble Report Code
∗61
Bypass Report Code
∗62
AC Loss Report Code
∗63
Low Bat Report Code
∗64
Test Report Code
Use Scheduling mode to set periodic test reports or use the
following key commands to set schedule 2 to the stated
repeat option (first test report sent 12 hours after command):
installer code +[#] + [0] + 0 = test report sent every 24 hours
installer code +[#] + [0] + 1 = test report sent once per week
installer code +[#] + [0] + 2 = test report sent every 28 days
∗65
Open Report Code
∗66
Arm Away/Stay Rpt Code
[0]
2nd Phone No.
Others
All
All
[2]
SIA Installations: delay
must be minimum of
30 seconds
[0]
[0]
[0]
[0]
[00]
|
[00]
|
[00]
|
[00]
|
[00]
|
[0]
[0,0]
Away Stay
∗67
RF Trans. Low Bat Report Code
UL: must be enabled if wireless devices are used
∗68
Cancel Report Code
RESTORE REPORT CODES
∗70
Alarm Restore Rpt Code
∗71
Trouble Restore Rpt Code
∗72
Bypass Restore Rpt Code
∗73
AC Restore Rpt Code
∗74
Low Bat Restore Rpt Code
∗75
RF Trans. Lo Bat Rst Rpt Code
UL: must be enabled if wireless devices are used
∗76
Test Restore Rpt Code
OUTPUT AND SYSTEM SETUP
∗77
Daylight Savings Time
Start\End Month
0 = Disabled
1-9 = January-September (1 = Jan, 2 = Feb, etc)
#+10 = October; #+11 = November; #+12 = December
∗78
Daylight Savings Time
Start\End Weekend
0 = disabled, 1 = first, 2 = second, 3 = third
4 = fourth, 5 = last, 6 = next to last, 7 = third to last
∗79 -*82
Menu Modes (see page 2 for description)
∗84
Auto Stay Arm
0 = no, 1 = yes, auto stay arm enabled
∗85
Cross Zone Timer
This option not for use in UL installations.
0 = 15 seconds
1 = 30 seconds
2 = 45 seconds
3 = 60 seconds
4 = 90 seconds
5 = 2 minutes
(assign cross zones on zone list 4, with *81 Menu mode)
∗86
Cancel Verify Keypad Display
0 = no, 1 = yes
∗87
Misc. Fault Delay Time
(used with Configurable Zone Type "digit 6")
0 = 15 seconds
1 = 30 seconds
2 = 45 seconds
3 = 60 seconds
4 = 90 seconds
5 = 2 minutes
UL: may only be used on non-burglar alarm/ non-fire alarm zones
when used in fire and/or UL burglar alarm installation
∗88
Program Mode Lockout Options
0 = standard *98 installer code lockout
(reentry only by [∗] + [#] within 50 seconds after power up)
1 = lockout [∗] + [#] reentry after *98 exit
2 = not used
3 = lockout all local programming after *98 exit (reentry via
downloader only)
– 4 –
[00]
[00]
[0]
[00]
[00]
[00]
[00]
[00]
[00]
[4][10]
[1][5]
[1]
[0]
6 = 2-1/2 min
#+12 = 8 min
7 = 3 min
#+13 = 10 min
8 = 4 min
#+14 = 12 min
9 = 5 min
#+15 = 15 min
#+10 = 6 min
#+11 = 7 min
[1]
[0]
6 = 2-1/2 min
#+12 = 8 min
7 = 3 min
#+13 = 10 min
8 = 4 min
#+14 = 12 min
9 = 5 min
#+15 = 15 min
#+10 = 6 min
#+11 = 7 min
[0]
|
|
|
|
|
|
|
|
|
|