Wiring your Detector

Power and Modbus data are wired between detectors with the first
connected to a control panel DETECTOR CHAIN terminal.
One example of such cable is BELDEN 3082A.
If you are encountering noise or irregular problems with a Modbus link, the problem is likely related
to grounding, incorrect shielding or wiring mains power next to Modbus wiring.
To ground the data cable, the shield should be connected to [-] of the chain terminals.
Reversing the [D+] and [D-] connections of any device can lead to the whole system to stop
working owing to reverse polarity found on the terminals.
Not appropriately grounding the device can give false readings, fail completely or turn into a
safety hazard!

Detector Chain ID Switches

When wiring multiple detectors in a chain it is important to identify each and
every detector installed for the control panel to receive and display accurate
data corresponding with the correct detector type.
The ID configuration diagram is printed onto detector boards for
quick reference. All detectors are factory set to ID1.
ID Switches must be configured for each and every detector connected to a
system to receive and display accurate data!
We recommend a plan, map and/or marking the detector enclosures detailing ID and location!
AGS Parksafe Panel - IOM Iss: 6 10-20
For MODBUS communications, a shielded cable is used.
The shielding can be of 2 types: braided [mesh of thin
conducting wires] or foil (consisting of a thin sheet of metal
covering the twisted wires).