Gree Versati II Series 서비스 매뉴얼 - 페이지 17

{카테고리_이름} Gree Versati II Series에 대한 서비스 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Gree Versati II Series 18 페이지. Air-to-water heat pump monobloc versati
Gree Versati II Series에 대해서도 마찬가지입니다: 매뉴얼 (13 페이지)

Gree Versati II Series 서비스 매뉴얼
Charging
valve 1
Notes
Discharge is allowed unless the unit has been stopped. (Cut off the power and repower it 1 minutes
later)
Protective measures should be taken during discharging to avoid frost bites.
When discharging is finished, if vacuuming cannot be done immediately, remove the hose to avoid air or
foreign matters entering the unit.
(2) Vacuuming: When discharging is finished, use hoses to connect the charging valve, manometer and
vacuum pump to vacuum the unit.
Note: when vacuuming is finished, pressure inside the unit should be kept lower than 80Pa for at least 30
minutes to make sure there is no leak. Either charging valve 1 or charging valve 2 can be used for vacuuming.
(3) Charging: when vacuuming is finished and it is certain that there is no leak, charging can be done.
Be sure to charge the specified amount of refrigerant in liquid state.
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to
change, preventing normal operation.
Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not.
With siphon tube
Test Operation & Troubleshooting & Maintenance
Connection Pipe
Vacuum pump
15
Pressure Meter
No siphon tube
Charging
valve 2