4.2

DIP Switch Settings for Pool and Spa Combination

S1 DIP Switch #
1
AUX1= any equipment
2
AUX2= any equipment
3
NOT USED
4
Heater cool down operates.
5
Normal operation
6
Separate Pool and Spa heater.
7
No solar system installed. Air temperature
is displayed.
8
After thermostat setting has been
reached, heater will remain OFF for 3
minutes.
S2 DIP Switch #
1
The AquaLink RS will be able to control a
Solar Heating system (If a solar sensor is
connected to the solar sensor input).
2
3
4
S1
OFF ON
1
2
3
4
5
6
7
4 3 2 1
4 3 2 1
6 5 4 3 2 1
8
1
RESET
AUTO
2
SERVICE
3
TIME OUT
4
S2
OFF
OFF
NOT USED
NOT USED
NOT USED
10 9 8 7 6 5 4 3 2 1
ON
AUX1= Pool Cleaner
AUX2= Low Speed for a two-speed filter pump.
Filter pump circuit becomes High Speed.
NOT USED
Heater cool down disabled.
Factory adjustment- when this switch is on,
temperature delays are eliminated and solar
temperature is displayed.
Do not leave this switch in the ON position.
Sharing one heater for pool and spa.
Changes air sensor to solar sensor. Air temperature
no longer displayed. Adjustable Freese Kit must be
added for freeze protection.
Heat Pump installed; after thermostat setting
has been reached, heater will remain OFF for 5
minutes.
ON
The AquaLink RS will be able to control a Heat
Pump. (The AquaLink RS will not be able to control
a Solar Heating system.)