Basic programming
Step 2: Set-up sensor functionality

Detection Mode

The Detection Mode for the output Channel 1 can be set to
behave in Presence or Absence mode:
 Presence mode allows a channel to turn on when
movement is detected. Once turned on, if no movement
is detected the Time Adjustment (10 minutes by
default) the channel will turn off.
 Absence mode requires the channel to be turned on by
some other means (e.g. by issuing a Scene Select
message via an Input Unit or IR Handset). Once turned
on, if no movement is detected for period of time (the
Time Adjustment) the channel will turn off.
In either case, sensitivity to movement of the Microwave
sensor (Channel 3) can be adjusted using the Sensitivity
parameter (set to 5 by default).
HINT: To assist in setting the Sensitivity, turn on the Walk
Test LED which will flash red when movement is detected.
By default when the detector turns on Local Scene 1 is
selected. When the detector turns off Local Scene 20 is
selected. See 'Scenes Used for Occupancy Detection' in
Step 3 for further details.
8
Switch Level On/Off
Occupancy detection can be made dependant on the
ambient light level using the Lux On Level and Lux Off
Level parameters.
Note: for applications where there is only one channel of lighting
being controlled in a room there is no need to select the channel
number.