Removing the Cable-Management Arm

Shut down and turn off the system you are removing and all peripherals attached to this
system.
At the back of the rack cabinet, disconnect and remove the AC power cable and all cables
connected to the back of the system and secured to the cable-management arm with the
arm's Velcro straps.
Loosen the two captive thumbscrews securing the cable-management arm retainer to the
vertical rack rails. See Figure 1-11.
Disconnect the inner tab of the cable-management arm from the cable tray.
Disconnect the outer tab of the cable-management arm from the cable tray.
Pull the cable-management arm from the cable tray.
Remove the two captive thumbscrews that secure the cable tray to the system. See
Figure 1-11.
Remove the cable tray.
Figure 1-11. Removing the Cable-Management Arm
captive thumbscrews (2)
latch on cable tray
cable-management
arm
tabs
back of
system
Tower-to-Rack and Rack-to-Tower Conversion Guide