Siemens SIPART PS2 기술 설명 - 페이지 11

{카테고리_이름} Siemens SIPART PS2에 대한 기술 설명을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens SIPART PS2 26 페이지. Mounting bracket kit
Siemens SIPART PS2에 대해서도 마찬가지입니다: 설치 지침 (4 페이지), 사용 설명서 (28 페이지), 설치 지침 (4 페이지), 하드웨어 설치 매뉴얼 (30 페이지), 간결한 사용 설명서 (35 페이지), 키트 설치 지침 (9 페이지), 설치 지침 (11 페이지)

Siemens SIPART PS2 기술 설명
Technical specifications
SIPART PS2 PA
Explosion protection to
ATEX
Mounting location
Permissible ambient temperature for
operation
At ≤ -10 °C (+14 °F) the display refresh
rate of the LCD is limited.
(for basic devices with Ex protection
the following applies: Only T4 is per-
module.)
missible when using I
y
Electrical data
Input
Power supply (terminals 6/7)
Bus voltage
• Bus connection with supply unit
- Max. supply voltage U
o
- Max. short-circuit current I
- Max. power P
o
• Bus connection with barrier
- Max. supply voltage (U
)
o
- Max. short-circuit current (I
- Max. power P
o
Current consumption
Additional fault current
Effective internal inductance L
Effective internal capacitance C
Safety shutdown can be activated with
coding bridge (terminals 81/82; elec-
trically isolated from the basic device)
• Input resistance
• Signal status "0" (shutdown active)
• Signal status "1" (shutdown not ac-
tive)
• Effective Internal capacitance C
• Effective internal inductance L
• For connection to power supply with –
- Max. supply voltage U
i
- Max. short-circuit current I
- Maximum power P
i
Electrical isolation
Test voltage
© Siemens AG 2008
Basic device
without Ex protection
Without
-30 ... +80 °C
(-22 ... +176 °F)
Bus-supplied
9 ... 32 V
o
)
o
11.5 mA ± 10%
0 mA
i
i
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
i
i
i
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
840 V DC, 1 s
Electropneumatic positioners
Basic device
Basic device
with Ex d protection
with Ex ia/ib protection
(flameproof casing)
Ex d
Ex ia/ib
II 2 G Ex d II C T4/T5/T6
II 2 G Ex ia/ib II C T6
Zone 1
Zone 1
T4: -30 ... +80 °C
T4: -30 ... +80 °C
(-22 ... +176 °F)
(-22 ... +176 °F)
T5: -30 ... +65 °C
T5: -30 ... +65 °C
(-22 ... +149 °F)
(-22 ... +149 °F)
T6: -30 ... +50 °C
T6: -30 ... +50 °C
(-22 ... +122 °F)
(-22 ... +122 °F)
Bus-supplied
Bus-supplied
9 ... 32 V
9 ... 24 V
Intrinsically safe
FISCO
17.5 V
380 mA
5.32 W
intrinsically safe
24 V
250 mA
1.2 W
11.5 mA ± 10%
11.5 mA ± 10%
0 mA
0 mA
8 μH
Negligible
> 20 kΩ
> 20 kΩ
0 ... 4.5 V or unused
0 ... 4.5 V or unused
13 ... 30 V
13 ... 30 V
Negligible
Negligible
Intrinsically safe
30 V
100 mA
1 W
Between basic device
The basic device and the
and the input for safety
input to the safety shut-
shutdown, as well as the
down, as well as the out-
outputs of the option
puts of the option
modules
modules, are individual,
intrinsically-safe circuits
840 V DC, 1 s
840 V DC, 1 s
SIPART PS2
Technical specifications
SIPART PS2 PA
Basic device
with Ex n/dust protec-
tion
Ex n
II 3 G Ex nA nL[nL] IIC T6
Dust
II 3 D Ex tD A22 IP66
T100°C
Zone 2/22
T4: -20 ... +75 °C
(-4 ... +167 °F)
T5: -20 ... +65 °C
(-4 ... +149 °F)
T6: -20 ... +50 °C
(-4 ... +122 °F)
Bus-supplied
9 ... 32 V
at "nA" and "tD":
Un = 32 V DC
at "nL":
FNICO
17.5 V
570 mA
at "nL"
32 V
11.5 mA ± 10%
0 mA
8 μH (at "nL")
Negligible
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
Negligible
Negligible
At "nA", "nL" and "tD"
30 V
100 mA
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
840 V DC, 1 s
Siemens FI 01 · 2009
6/11