Cisco Firepower 2130 설치 및 유지 관리 - 페이지 13
{카테고리_이름} Cisco Firepower 2130에 대한 설치 및 유지 관리을 온라인으로 검색하거나 PDF를 다운로드하세요. Cisco Firepower 2130 26 페이지. Rack-mount and ground the chassis
Cisco Firepower 2130에 대해서도 마찬가지입니다: 매뉴얼 (12 페이지), 배포 매뉴얼 (8 페이지), 시작하기 (42 페이지)
Installation, Maintenance, and Upgrade
Do not strip more than the recommended length of wire because doing so could leave the wire exposed from
Note
the terminal block.
Figure 5: Stripped DC Input Source Wire
1
Strip the wires to approximately 0.39 inch (10 mm) +
0.02 inch (0.5 mm)
Step 4
Insert the exposed wire into the terminal block. Make sure that you cannot see any wire lead outside the plastic cover.
Only wires with insulation should extend from the terminal block.
Step 5
Use a screwdriver to tighten the terminal block captive screws.
Do not over torque the terminal block captive screws. Make sure that the connection is snug, but the wire is
Caution
not crushed. Verify by tugging lightly on each wire to make sure that they do not move.
Connect the DC Power Supply Module
—
Installation, Maintenance, and Upgrade
13