NTP-A119 Install the Alarm Expansion Panel
Figure 1-1
Step 4
Continue with the
to install an alarm expansion panel (AEP). If not, continue with the
Timing, LAN, and Craft Pin Connections" procedure on page
Stop. You have completed this procedure.
NTP-A119 Install the Alarm Expansion Panel
Purpose
Tools/Equipment
Prerequisite Procedures
Cisco ONS 15454 Procedure Guide, R5.0
1-12
Installing the Fan-Tray Assembly
FA N
FA IL
C R
IT
M A
J
M IN
LCD
Fan tray
assembly
"NTP-A119 Install the Alarm Expansion Panel" procedure on page 1-12
This procedure installs an alarm expansion panel (AEP) onto the
15454-SA-ANSI or 15454-SA-HD shelf backplane. The AEP provides
alarm contacts in addition to the 16 provided by the AIC-I card. Typically,
the AEP is preinstalled when ordered with the ONS 15454; however, the
AEP can be ordered separately. The AIC-I card must be installed before
you can provision the alarm contacts enabled by the AEP.
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Wire wrapper
6-pair #29 AWG double-shielded cable
Standoffs (4)
DLP-A10 Remove the Lower Backplane Cover, page 17-10
Chapter 1
Install the Shelf and Backplane Cable
"NTP-A8 Attach Wires to Alarm,
1-15.
if you plan
March 2005